600/1000V Mica+ XLPE Insulated, Armoured LSZH Sheathed Power Cables (Single Core)

FFX300 1mRMAZ1-R(CU/MGT+XLPE/LSZH/AWA/LSZH 600/1000V Class 2)

APPLICATION

This cable is designed for areas where the integrity of the electrical circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground tunnels, communications systems, sewage treatment plants, lifts, escalators, and high-rise buildings.

images/600-1000V Mica+ Armoured LSZH Sheathed Power Cables (Single Core).jpg images/ Mica+ Armoured LSZH Sheathed Power Cables.jpg

STANDARDS

  • Basic design to IEC 60502-1

FIRE PERFORMANCE

Circuit Integrity IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); CEI 20-36/2-1; SS299-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1)
System circuit integrity DIN 4102-12, E30 depending on lay system
Flame Retardance (Single Vertical Wire Test) EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454

Note: Asterisk * denotes superseded standard.

VOLTAGE RATING

600/1000 V

CABLE CONSTRUCTION

Conductors Plain annealed copper wire, stranded according to IEC 60228 class 2
Insulation Mica glass tape covered by extruded XLPE compound
Inner Sheath Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1
Armouring Aluminum wire armour
Outer Sheath Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option

COLOUR CODE

Insulation colour upon request  
Sheath Colour Black (other colours upon request)

PHYSICAL AND THERMAL PROPERTIES

Temperature range during operation (fixed state) -30°C – +90°C
Temperature range during installation (mobile state) -20°C – +50°C
Minimum bending radius 10 x Overall Diameter

ELECTRICAL PROPERTIES

Dielectric test 3500 V r.m.s. x 5' (core/core)
Insulation resistance 1000 MΩ x km (at 20°C)
Short circuit temperature 250°C

CONSTRUCTION PARAMETERS

Conductor FFX300 1mRMAZ1-R
Nominal Cross Section Area No./Nominal Diameter of Strands Diameter of Conductor Nominal Insulation Thickness Approx. Overall Diameter Approx. Weight
mm2 No./mm mm mm mm kg/km
50 19/1.78 8.9 1.0 18.5 780
70 19/2.14 10.7 1.1 20.5 1010
95 19/2.52 12.6 1.1 23 1320
120 37/2.03 14.21 1.2 24.5 1610
150 37/2.25 15.75 1.4 27 2010
185 37.2.52 17.64 1.6 29.5 2440
240 61/2.25 20.25 1.7 34.5 3060
300 61/2.52 22.68 1.8 36.9 3690
400 65/2.85 25.65 2.0 41.5 4780
500 61/3.20 28.8 2.2 45.5 5970
630 127/2.52 32.76 2.4 50.5 7530
800 127/2.85 37.05 2.6 56.8 9680
1000 127/3.20 41.6 2.8 61.5 11980

ELECTRICAL PROPERTIES

Conductor Operating Temperature 90°C
Ambient Temperature 30°C

Current-Carrying Capacities(Amp)

Conductor cross-sectional area Reference Method C (clipped direct) Reference Method F (in free air or on a perforated cable tray, horizontal or vertical)
  Touching Touching Spaced by on cable diameter
  2 cables, single-phase a.c. or d.c. flat 3 or 4 cables,three-phase a.c. flat 2 cables, single-phase a.c. or d.c. flat 3 or 4 cables, three-phase a.c. flat 3 cables three-phase a.c. trefoil 2 cables, d.c. 2 cables, single-phase a.c. 3 or 4cables, three-phase a.c.
Horizontal Vertical Horizontal Vertical Horizontal Vertical
1 2 3 4 5 6 7 8 9 10 11 12
mm2 A A A A A A A A A A A
50 237 220 253 232 222 284 270 282 266 288 266
70 303 277 322 293 285 356 349 357 337 358 331
95 367 333 389 352 346 446 426 436 412 425 393
120 425 383 449 405 402 519 497 504 477 485 449
150 488 437 516 462 463 600 575 566 539 549 510
185 557 496 587 524 529 688 660 643 614 618 574
240 656 579 689 612 625 815 782 749 714 715 666
300 755 662 792 700 720 943 906 842 805 810 755
400 853 717 899 767 815 1137 1094 929 889 848 797
500 962 791 1016 851 918 1314 1266 1032 989 923 871
630 1082 861 1146 935 1027 1528 1474 1139 1092 992 940
800 1170 904 1246 987 1119 1809 1744 1204 1155 1042 978
1000 1261 961 1345 1055 1214 2100 2026 1289 1238 1110 1041

Voltage Drop (Per Amp Per Meter)

Nominal Cross Section Area 1 2 cables d.c.2 Ref. Methods C&F(clipped direct, on trays or in free air)
2 cables, single-phase a.c. 3 or 4 cables, three-phase a.c.
Touching 3 Spaced* 4 Trefoil and touching 5 Flat and touching 6 Flat and spaced*7
mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
r x z r x z r x z r x z r x z
50 0.98 0.99 0.21 1.00 0.98 0.29 1.00 0.86 0.180 0.87 0.84 0.25 0.88 0.84 0.33 0.90
70 0.67 0.68 0.20 0.71 0.69 0.29 0.75 0.59 0.170 0.62 0.60 0.25 0.65 0.62 0.32 0.70
95 0.49 0.51 0.195 0.55 0.53 0.28 0.60 0.44 0.170 0.47 0.46 0.24 0.52 0.49 0.31 0.58
120 0.39 0.41 0.190 0.45 0.43 0.27 0.51 0.35 0.165 0.39 0.38 0.34 0.44 0.41 0.30 0.51
150 0.31 0.33 0.185 0.38 0.36 0.27 0.45 0.29 0.160 0.33 0.31 0.23 0.39 0.34 0.39 0.45
185 0.25 0.27 0.185 0.33 0.30 0.26 0.40 0.23 0.160 0.28 0.26 0.23 0.34 0.29 0.29 0.41
240 0.195 0.21 0.180 0.28 0.24 0.26 0.35 0.180 0.155 0.24 0.21 0.22 0.30 0.24 0.28 0.37
300 0.155 0.17 0.175 0.25 0.195 0.25 0.32 0.145 0.150 0.21 0.170 0.22 0.28 0.20 0.27 0.34
400 0.115 0.145 0.170 0.22 0.180 0.24 0.30 0.125 0.150 0.195 0.160 0.21 0.27 0.20 0.27 0.33
500 0.093 0.125 0.170 0.21 0.165 0.24 0.29 0.105 0.145 0.180 0.145 0.20 0.25 0.190 0.24 0.31
630 0.073 0.105 0.165 0.195 0.150 0.23 0.27 0.092 0.145 0.170 0.135 0.195 0.24 0.175 0.23 0.29
800 0.056 0.090 0.160 0.190 0.145 0.23 0.27 0.086 0.140 0.165 0.130 0.180 0.23 0.175 0.195 0.26
1000 0.045 0.092 0.155 0.180 0.140 0.21 0.25 0.080 0.135 0.155 0.125 0.170 0.21 0.165 0.180 0.24

Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance