600/1000V Mica+ XLPE Insulated, Armoured LSZH Sheathed Power Cables (Single Core)
FFX300 1mRMAZ1-R(CU/MGT+XLPE/LSZH/AWA/LSZH 600/1000V Class 2)
APPLICATION
This cable is designed for areas where the integrity of the electrical circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground tunnels, communications systems, sewage treatment plants, lifts, escalators, and high-rise buildings.
STANDARDS
- Basic design to IEC 60502-1
FIRE PERFORMANCE
Circuit Integrity |
IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); CEI 20-36/2-1; SS299-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) |
System circuit integrity |
DIN 4102-12, E30 depending on lay system |
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free |
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1; BS 6425-1* |
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2; BS 6425-2* |
Minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases |
NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
600/1000 V
CABLE CONSTRUCTION
Conductors |
Plain annealed copper wire, stranded according to IEC 60228 class 2 |
Insulation |
Mica glass tape covered by extruded XLPE compound |
Inner Sheath |
Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 |
Armouring |
Aluminum wire armour |
Outer Sheath |
Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option |
COLOUR CODE
Insulation colour upon request |
|
Sheath Colour |
Black (other colours upon request) |
PHYSICAL AND THERMAL PROPERTIES
Temperature range during operation (fixed state) |
-30°C – +90°C |
Temperature range during installation (mobile state) |
-20°C – +50°C |
Minimum bending radius |
10 x Overall Diameter |
ELECTRICAL PROPERTIES
Dielectric test |
3500 V r.m.s. x 5' (core/core) |
Insulation resistance |
1000 MΩ x km (at 20°C) |
Short circuit temperature |
250°C |
CONSTRUCTION PARAMETERS
Conductor |
FFX300 1mRMAZ1-R |
Nominal Cross Section Area |
No./Nominal Diameter of Strands |
Diameter of Conductor |
Nominal
Insulation Thickness |
Approx.
Overall Diameter |
Approx.
Weight |
mm2 |
No./mm |
mm |
mm |
mm |
kg/km |
50 |
19/1.78 |
8.9 |
1.0 |
18.5 |
780 |
70 |
19/2.14 |
10.7 |
1.1 |
20.5 |
1010 |
95 |
19/2.52 |
12.6 |
1.1 |
23 |
1320 |
120 |
37/2.03 |
14.21 |
1.2 |
24.5 |
1610 |
150 |
37/2.25 |
15.75 |
1.4 |
27 |
2010 |
185 |
37.2.52 |
17.64 |
1.6 |
29.5 |
2440 |
240 |
61/2.25 |
20.25 |
1.7 |
34.5 |
3060 |
300 |
61/2.52 |
22.68 |
1.8 |
36.9 |
3690 |
400 |
65/2.85 |
25.65 |
2.0 |
41.5 |
4780 |
500 |
61/3.20 |
28.8 |
2.2 |
45.5 |
5970 |
630 |
127/2.52 |
32.76 |
2.4 |
50.5 |
7530 |
800 |
127/2.85 |
37.05 |
2.6 |
56.8 |
9680 |
1000 |
127/3.20 |
41.6 |
2.8 |
61.5 |
11980 |
ELECTRICAL PROPERTIES
Conductor Operating Temperature |
90°C |
Ambient Temperature |
30°C |
Current-Carrying Capacities(Amp)
Conductor cross-sectional area |
Reference Method C (clipped direct) |
Reference Method F (in free air or on a perforated cable tray, horizontal or vertical) |
|
Touching |
Touching |
Spaced by on cable diameter |
|
2 cables, single-phase a.c. or d.c. flat |
3 or 4 cables,three-phase a.c. flat |
2 cables, single-phase a.c. or d.c. flat |
3 or 4 cables, three-phase a.c. flat |
3 cables three-phase a.c. trefoil |
2 cables, d.c. |
2 cables, single-phase a.c. |
3 or 4cables, three-phase a.c. |
Horizontal |
Vertical |
Horizontal |
Vertical |
Horizontal |
Vertical |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
50 |
237 |
220 |
253 |
232 |
222 |
284 |
270 |
282 |
266 |
288 |
266 |
70 |
303 |
277 |
322 |
293 |
285 |
356 |
349 |
357 |
337 |
358 |
331 |
95 |
367 |
333 |
389 |
352 |
346 |
446 |
426 |
436 |
412 |
425 |
393 |
120 |
425 |
383 |
449 |
405 |
402 |
519 |
497 |
504 |
477 |
485 |
449 |
150 |
488 |
437 |
516 |
462 |
463 |
600 |
575 |
566 |
539 |
549 |
510 |
185 |
557 |
496 |
587 |
524 |
529 |
688 |
660 |
643 |
614 |
618 |
574 |
240 |
656 |
579 |
689 |
612 |
625 |
815 |
782 |
749 |
714 |
715 |
666 |
300 |
755 |
662 |
792 |
700 |
720 |
943 |
906 |
842 |
805 |
810 |
755 |
400 |
853 |
717 |
899 |
767 |
815 |
1137 |
1094 |
929 |
889 |
848 |
797 |
500 |
962 |
791 |
1016 |
851 |
918 |
1314 |
1266 |
1032 |
989 |
923 |
871 |
630 |
1082 |
861 |
1146 |
935 |
1027 |
1528 |
1474 |
1139 |
1092 |
992 |
940 |
800 |
1170 |
904 |
1246 |
987 |
1119 |
1809 |
1744 |
1204 |
1155 |
1042 |
978 |
1000 |
1261 |
961 |
1345 |
1055 |
1214 |
2100 |
2026 |
1289 |
1238 |
1110 |
1041 |
Voltage Drop (Per Amp Per Meter)
Nominal Cross Section Area 1 |
2 cables d.c.2 |
Ref. Methods C&F(clipped direct, on trays or in free air) |
2 cables, single-phase a.c. |
3 or 4 cables, three-phase a.c. |
Touching 3 |
Spaced* 4 |
Trefoil and touching 5 |
Flat and touching 6 |
Flat and spaced*7 |
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
|
|
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
50 |
0.98 |
0.99 |
0.21 |
1.00 |
0.98 |
0.29 |
1.00 |
0.86 |
0.180 |
0.87 |
0.84 |
0.25 |
0.88 |
0.84 |
0.33 |
0.90 |
70 |
0.67 |
0.68 |
0.20 |
0.71 |
0.69 |
0.29 |
0.75 |
0.59 |
0.170 |
0.62 |
0.60 |
0.25 |
0.65 |
0.62 |
0.32 |
0.70 |
95 |
0.49 |
0.51 |
0.195 |
0.55 |
0.53 |
0.28 |
0.60 |
0.44 |
0.170 |
0.47 |
0.46 |
0.24 |
0.52 |
0.49 |
0.31 |
0.58 |
120 |
0.39 |
0.41 |
0.190 |
0.45 |
0.43 |
0.27 |
0.51 |
0.35 |
0.165 |
0.39 |
0.38 |
0.34 |
0.44 |
0.41 |
0.30 |
0.51 |
150 |
0.31 |
0.33 |
0.185 |
0.38 |
0.36 |
0.27 |
0.45 |
0.29 |
0.160 |
0.33 |
0.31 |
0.23 |
0.39 |
0.34 |
0.39 |
0.45 |
185 |
0.25 |
0.27 |
0.185 |
0.33 |
0.30 |
0.26 |
0.40 |
0.23 |
0.160 |
0.28 |
0.26 |
0.23 |
0.34 |
0.29 |
0.29 |
0.41 |
240 |
0.195 |
0.21 |
0.180 |
0.28 |
0.24 |
0.26 |
0.35 |
0.180 |
0.155 |
0.24 |
0.21 |
0.22 |
0.30 |
0.24 |
0.28 |
0.37 |
300 |
0.155 |
0.17 |
0.175 |
0.25 |
0.195 |
0.25 |
0.32 |
0.145 |
0.150 |
0.21 |
0.170 |
0.22 |
0.28 |
0.20 |
0.27 |
0.34 |
400 |
0.115 |
0.145 |
0.170 |
0.22 |
0.180 |
0.24 |
0.30 |
0.125 |
0.150 |
0.195 |
0.160 |
0.21 |
0.27 |
0.20 |
0.27 |
0.33 |
500 |
0.093 |
0.125 |
0.170 |
0.21 |
0.165 |
0.24 |
0.29 |
0.105 |
0.145 |
0.180 |
0.145 |
0.20 |
0.25 |
0.190 |
0.24 |
0.31 |
630 |
0.073 |
0.105 |
0.165 |
0.195 |
0.150 |
0.23 |
0.27 |
0.092 |
0.145 |
0.170 |
0.135 |
0.195 |
0.24 |
0.175 |
0.23 |
0.29 |
800 |
0.056 |
0.090 |
0.160 |
0.190 |
0.145 |
0.23 |
0.27 |
0.086 |
0.140 |
0.165 |
0.130 |
0.180 |
0.23 |
0.175 |
0.195 |
0.26 |
1000 |
0.045 |
0.092 |
0.155 |
0.180 |
0.140 |
0.21 |
0.25 |
0.080 |
0.135 |
0.155 |
0.125 |
0.170 |
0.21 |
0.165 |
0.180 |
0.24 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance